Generic filters
Generic filters

VANGUARD wireless gas detector for toxic and combustible

The Vanguard WirelessHART gas detector from UNITED ELECTRIC is ideal for monitoring toxic and combustible gases without costly, fixed wiring.

With a five-year battery life and a calibration button, the Vanguard detector is easy to operate and maintain. Each detector has a WirelessHART transceiver, antenna, display, long-lasting power module, gas sensor and signal processor for the gas sensor.

Vanguard uses a sensor architecture with the “Flexsense”trademark, which allows the sensor to identify its target gas and self-configure itself to a Vanguard transmitter when connected.

It is currently available with either a non-dispersive (0-100% LEL) infrared methane sensor (NDIR) or an electrochemical hydrogen sulfide sensor (0-100 ppm).

ADVANTAGE

  • Wireless capability

  • Interchangeable sensors for toxic and combustible gases

  • Interoperable with existing wirelessHART networks and asset management systems (AMS)

  • Easy calibration and operation

  • 5 + years battery life

  • Heavy duty design with hazardous area approvals Class 1, Div 1 and 2

APPLICATIONS

  • Remote and local wireless gas detection
  • Temporary situations in which the cost of establishing a wired solution is completely unfeasible
  • Asset management initiatives

CHARACTERISTICS

  • Operating temperature: -20 ° C to 50 ° C
  • Supported gases: Methane (CH₄); Hydrogen sulfide (H₂S)
  • Resolution: 1% LEL o 1ppm
  • Accuracy: ± 2% LEL (sensor CH₄); ± 10 PPM (sensor H₂S)
  • Repeatability: ± 2% LEL (sensor CH₄); ± 10 PPM (sensor H₂S)
  • Enclosure: Type 4X
  • Weight: 9.6 lbs (including sensor and battery)